Activating / deactivating ELEMENT / deactivating,
Perform the following steps to deactivate a digital element:
Deactivating a
digital element
Step
NOTE:
You can only perform a reset if the corresponding element is deactivated.
In order to reverse the impact of activation, you first have to reverse the activation itself and not
i
just its impacts.
This is particularly important for control elements.
A command element is used to switch off all zones in a section. It has been activated using the
Example
'Activate element' command.
You do not reset to the original condition by switching on all zones in this section but by deac-
tivating the active command element. Otherwise the zones would switch on but the command
element would remain active.
60
Building Technologies
Fire Safety
Action
Select alarm message of the cor-
1
responding digital object using the
scroll keys on the display.
Press softkey
2
<Functions for sel. message..>
Press softkey
3
<Select ELEMENT¯>
Press softkey
4
<More functions..>
Press softkey
5
<DEACTIVATE element>
Press button <Reset>,
6
to reset the alarm message
Operating instructions Œ•Ž
continued
Result / Comment
The zone selected is displayed in-
versely
The corresponding element is dis-
played inversely
Implementation messages
'Implementing ...'
'Implemented'
The alarm message disappears