Changing detector PARAMETER SET

It is mainly used to temporarily switch detectors to a less sensitive setting, e.g. when work is be-
When is this
ing carried out (as alternative to the 'Renovation' operating mode).
function used?
F
Parameter sets
You will find a detailed list of the parameter sets available in the chapter "Detector parameter
available
sets" on page 121 (section "Basic system information &").
· For interactive detectors only, and only if this function has been approved by the service en-
i
gineer.
· Only security personnel may temporarily change parameter sets.
· Attention: Each temporary adjustment is automatically reset when the station is restarted.
If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess
Perform the following steps to set another parameter set:
Changing pa-
rameter set
Step
64
Building Technologies
Fire Safety
Action
Navigate to the ELEMENT you want us-
1
ing:
<Browse FIRE DETECTION..>
<Browse EXTINGUISHING..>
<Select SECTION¯>
<Selected ZONE¯>
<Select ELEMENT¯>
Press softkey
2
<Parameter sets functions..>
Press softkey
3
<CHANGE parameter set.>
Press softkey
4
<Next parameter set.>
Press softkey
5
<Operate..>
t
<Browse..>
t
- or -
t
t
t
<Set>
Operating instructions Œ•Ž
Result / Comment
The element functions are dis-
played
Repeat this step until the corre-
sponding parameter set is found
Implementation messages
'Implementing ...'
'Implemented'
A6V10225450_b_en_--
2017.09.07
- and -