TEST CONDITION per SECTION

Automatic detectors (or manual call points) are normally tested at section level; but they can
Information
also be tested at line or zone level.
about the 'Test
condition' oper-
An element (i.e. an individual fire detector or manual call point) cannot be set to the 'Test
ating mode
condition' operating mode.
Sections and zones in 'Test condition' operating mode are spontaneously displayed as mes-
sages of the 'Isolation' category.
The command is available for lines with Sinteso
For which lines
collective devices.
is this function
available?
When a device is activated, its response indicator flashes for a few seconds, and an appropriate
How does it
message is displayed during this time on the terminal.
work?
When in this operating mode, the response time is shorter.
No alarm messages are generated!
Per SECTION means all detector (or manual call point) zones within a SECTION.
What does 'per -
SECTION'
mean?
The steps for TEST and TEST OFF for fire detectors also apply to manual call points.
NOTE
This chapter shows how the 'Test condition' operating mode is switched on / off.
Using this chap-
+
ter
You will find a description of how the test is actually carried out in the chapters
· "Testing AUTOMATIC DETECTORS " on page 47
· "Testing MANUAL CALL POINTS " on page 48
If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess