Panasonic MINAS-A5NL Series Technical Reference page 114

Ac servo driver
Hide thumbs Also See for MINAS-A5NL Series:
Table of Contents

Advertisement

(2) When following to command (Pr7.40-bit0=1)
During magnetic pole position estimation, even if servo is on (motor is in activated state), turn Servo_Active
bit of RTEX status to 0.
After completion of magnetic pole position estimation, Servo_Active bit of RTEX status is turned to 1.
Example: Movement during CP control, Pr7.43=7
1 After control power is turned on, if turning servo on (make Servo_On bit 1), motor is activated while
Servo_Active bit remains to be 0 and magnetic pole position estimation is implemented.
2. During magnetic pole position estimation, magnetic pole detection completion output
(SI-MON4/EX-SON bit) and Servo_Active bit are turned to be 0. During this, set command position of
upper device to value of actual position (APOS) and make command position follow actual position
(APOS).
When magnetic pole position estimation is completed normally, magnetic pole detection completion
output (SI-MON4/EX-SON bit) and Servo_Active bit are turned to be 1.
Command
code
Servo_Ready
Servo_On
Motor power supply
Servo_Active
SI-MON4/EX-SON
(Pole detected output)
Position
*1) Be careful that the motor power is supplied but the Servo Active bit is zero while estimating pole position.
R2.0
Turn ON the main circuit and control power
**h
20h
0
1
0
1
No power supply
0
Estimating pole position
0
Actual position
Track the instructed position while detecting pole position
Power supply *1)
1
1
Instructed position
Instructed position
Instructed position valid
Motor Business Division, Appliances Company, Panasonic Corporation
No. SX-DSV02310 - 106 -
Time

Advertisement

Table of Contents
loading

Table of Contents