Electrical connection

Observe Chapter, "Safety instructions" when carrying out any work at the converter.
See also
Safety information (Page 15)
Insufficient degree of protection as a result of inadequate sealing of the cable entry
If the cable entry is not correctly sealed, it is possible that the drive no longer complies with
the requirements for the specified degree of protection.
If the drive is operated with an insufficient degree of protection, death, serious injury, and
material damage can result.
To maintain the drive's degree of protection, after connecting the cable, seal the cable entries
so they are air-tight immediately.
Insufficient degree of protection as a result of modifying the floor/roof panel
If you make any changes to the floor panel or the roof panel in order to modify the cable entry,
the changes may result in the drive no longer meeting the requirements for the degree of
protection shown. If there are holes in the floor or roof panel, then animals and vermin, for
example, can get into drive during operation.
If the drive is operated with an insufficient degree of protection, death, serious injury, and
material damage can result.
To maintain the drive's degree of protection, seal the holes so they are air-tight immediately
after installation.
Defective seals
When working on the device, seals at the doors, roof panels as well as front, rear and side
panels can be damaged. Operating the device with defective seals can result in death, serious
injury or material damage.
Replace the defective seals before commissioning. Observe the environmental conditions
stated in the technical data.
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions 04/2017
WARNING
WARNING
WARNING
6
73