Mounting
5.4 Mounting fans
Install the transport units in accordance with the specifications provided in the accompanying
dimension drawings. When doing this, maintain the specified distance between the top of the
cabinet and the ceiling.
5.4
Mounting fans
You must mount the fans, if, for logistical reasons, the fans were separately supplied. Proceed
as described in the section "Mounting fans" of Chapter "Replacing fans".
See also
Replacing a fan (Page 109)
5.5
Ensuring cooling air
The cooling air for the power unit is drawn in from the front through the ventilation grilles in the
cabinet doors. The warmed air is expelled above the fan through the perforated top cover or
the ventilation grilles in the top cover.
Make sure that the air that is supplied is free of dust or any other electrically conductive
material. Avoid environmental conditions that could cause condensation. Seal the cable
connector panels from the top.
72
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions 04/2017