● Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
● Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions 04/2017
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
Shield busbar
Shielded cable
Mounting clip
Figure 6-1
Shield connection using a clip
NOTICE
Damaged or incorrectly mounted cable shielding
Incorrect connection or damaging of the cable shield can impair the function of the system.
● Handle the cable shield carefully.
● Ensure that the cable shield is correctly connected.
impedance and through the largest possible surface area.
Shield busbars
Cables
Terminals
Figure 6-2
Bridging shield gaps
Electrical connection
6.1 Electromagnetic compatibility
77