Power Unit Components; Power Unit Components Of A Starting Converter (6/6-Pulse Drive System); Thyristors; Figure 3-1 Components Of A Starting Converter For A 6/6-Pulse Drive System - Siemens SINAMICS GL150 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Description
3.3 Power unit
● Line-side and machine-side overvoltage protection with spark-gap-free metal-oxide surge
● DC link reactor for decoupling the line-side converter from the motor-side converter
● Power cables connected from below
3.3.2

Power unit components

3.3.2.1

Power unit components of a starting converter (6/6-pulse drive system)

The diagram below shows an example of the typical components of a starting converter for a
6/6-pulse drive system:
Circuit breaker
Surge suppressor (metal-oxide disks, without spark gaps)
Line-side converter
Air-cooled DC link reactor, installed in a cabinet
Motor-side converter
Motor voltage sensing (U
Current transformer in the DC link
Converter transformer
Synchronizing transformer or converter
Figure 3-1
Components of a starting converter for a 6/6-pulse drive system
3.3.2.2

Thyristors

One or two of the thyristor stacks are used for a 6-pulse bridge. They differ in the number of
pick-offs from the heat sinks. The thyristor stacks are equipped with various thyristors and
corresponding RC (resistor, capacitor) circuitry. Six thyristors are braced in one clamped
thyristor assembly.
30
arresters
sensing)
M
SINAMICS GL150 6SL38503UM114PA0Z
Operating Instructions 04/2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents