2818 Fast tasks
2819 Parameter thread
2820 LCP stack overflow
2821 Serial port overflow
2822 USB port overflow
3072-5
Parameter value is outside its limits.
122
Perform a initialization. Parameter num-
ber causing the alarm: Subtract the code
from 3072. Ex Error code 3238:
3238-3072 = 166 is outside the limit
5123 Option in slot A: Hardware incompatible
with Control board hardware
5124 Option in slot B: Hardware incompatible
with Control board hardware
5125 Option in slot C0: Hardware incompati-
ble with Control board hardware
5126 Option in slot C1: Hardware incompati-
ble with Control board hardware
5376-6
Out of memory
231
WARNING 40
Overload of Digital Output Terminal 27:
Check the load connected to terminal 27 or re-
move short-circuit connection. Check parameters
5-00 and 5-01.
WARNING 41
Overload of Digital Output Terminal 29:
Check the load connected to terminal 29 or re-
move short-circuit connection. Check parameters
5-00 and 5-02.
WARNING 42
Overload of Digital Output On X30/6 :
Check the load connected to X30/6 or remove
short-circuit connection. Check parameter 5-32.
WARNING 42
Overload of Digital Output On X30/7 :
Check the load connected to X30/7 or remove
short-circuit connection. Check parameter 5-33.
WARNING 47
24 V supply low:
The external 24 V DC backup power supply may
be overloaded, otherwise Contact your Danfoss
supplier.
WARNING 48
1.8 V supply low:
Contact your Danfoss supplier.
WARNING 49
Speed limit:
The speed is not within the specified range in par.
4-11 and par. 4-13.
Warnings and Alarms
ALARM 50
AMA calibration failed:
Contact your Danfoss supplier.
ALARM 51
AMA check Unom and Inom:
The setting of motor voltage, motor current, and
motor power is presumably wrong. Check the set-
tings.
ALARM 52
AMA low Inom:
The motor current is too low. Check the settings.
ALARM 53
AMA motor too big:
The motor is too big for the AMA to be carried out.
ALARM 54
AMA motor too small:
The motor is too big for the AMA to be carried out.
ALARM 55
AMA par. out of range:
The par. values found from the motor are outside
acceptable range.
ALARM 56
AMA interrupted by user:
The AMA has been interrupted by the user.
ALARM 57
AMA timeout:
Try to start the AMA again a number of times, until
the AMA is carried out. Please note that repeated
runs may heat the motor to a level where the re-
sistance Rs and Rr are increased. In most cases,
however, this is not critical.
ALARM 58
AMA internal fault:
Contact your Danfoss supplier.
WARNING 59
Current limit:
Contact your Danfoss supplier.
WARNING 61
Encoder loss:
Contact your Danfoss supplier.
WARNING 62
Output Frequency at Maximum Limit:
The output frequency is higher than the value set
in par. 4-19
MG.33.A8.02 - VLT is a registered Danfoss trademark