11.2. Modbus RTU Communications

11.2.1. Modbus Telegram Structure
The Optidrive Eco supports Master / Slave Modbus RTU communications, using the 03 Read Multiple Holding Registers and 06 Write Single
Holding Register commands. Many Master devices treat the first Register address as Register 0; therefore it may be necessary to convert the
Register Numbers detail in section 11.2.2 by subtracting 1 to obtain the correct Register address. The telegram structure is as follows:-
11.2.2. Modbus Control & Monitoring Registers
The following is a list of accessible Modbus Registers available in the Optidrive Eco.
When Modbus RTU is configured as the Fieldbus option, all of the listed registers can be accessed.
Registers 1 and 2 can be used to control the drive providing that Modbus RTU is selected as the primary command source (P1-12 =
4) and no Fieldbus Option Module is installed in the drive Option Slot.
Register 4 can be used to control the acceleration and deceleration rate of the drive providing that Fieldbus Ramp Control is
enabled (P5-07 = 1)
Registers 6 to 24 can be read regardless of the setting of P1-12
Register
Upper Byte
Number
Command Control Word
1
2
Command Speed Reference
3
Reserved
Command Ramp times
4
Error code
Drive status
6
7
Output Frequency
8
Output Current
9
Output Torque
10
Output Power
11
Digital Input Status
20
Analog 1 Level
21
Analog 2 Level
42
Optidrive Eco User Guide Revision 2.01
Command 03 – Read Holding Registers
Master Telegram
Length
Slave Address
1
Function Code (03)
1
st
1
Register Address
2
No. Of Registers
2
CRC Checksum
2
Command 06 – Write Single Holding Register
Master Telegram
Length
Slave Address
1
Function Code (06)
1
Register Address
2
Value
2
CRC Checksum
2
Lower Byte
Read
Notes
Write
R/W
Command control word used to control the Optidrive when operating with
Modbus RTU. The Control Word bit functions are as follows :-
Bit 0 : Run/Stop command. Set to 1 to enable the drive. Set to 0 to stop the drive.
Bit 1 : Fast stop request. Set to 1 to enable drive to stop with 2
ramp.
Bit 2 : Reset request. Set to 1 in order to reset any active faults or trips on the
drive.
This bit must be reset to zero once the fault has been cleared.
Bit 3 : Coast stop request. Set to 1 to issue a coast stop command.
R/W
Set-point must be sent to the drive in Hz to one decimal place, e.g. 500 = 50.0Hz
R/W
No Function
R/W
This register specifies the drive acceleration and deceleration ramp times used
when Fieldbus Ramp Control is selected (P5-08 = 1) irrespective of the setting of
P1-12. The input data range is from 0 to 60000 (0.00s to 600.00s)
R
This register contains 2 bytes.
The Lower Byte contains an 8 bit drive status word as follows :-
Bit 0 : 0 = Drive Disabled (Stopped), 1 = Drive Enabled (Running)
Bit 1 : 0 = Drive Healthy, 1 = Drive Tripped
Bit 3 :Inhibit
Bit 4 : Service due
Bit 5 : Standby
Bit 6 : Drive Ready
Bit 7 : 0 = Normal condition, 1 = Low or High Load condition detected
The Upper Byte will contain the relevant fault number in the event of a drive trip.
Refer to section 13.1 for a list of fault codes and diagnostic information
R
Output frequency of the drive to one decimal place, e.g.123 = 12.3 Hz
R
Output current of the drive to one decimal place, e.g.105 = 10.5 Amps
R
Motor output torque level to one decimal place, e.g. 474 = 47.4 %
R
Output power of the drive to two decimal places, e.g.1100 = 11.00 kW
R
Represents the status of the drive inputs where Bit 0 = Digital Input 1 etc.
R
Analog Input 1 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%
R
Analog Input 2 Applied Signal level in % to one decimal place, e.g. 1000 = 100.0%
Slave Response
Byte
Slave Address
Byte
Function Code (03)
Bytes
Starting Address
st
Bytes
1
Register Value
nd
Bytes
2
Register Value
Etc...
CRC Checksum
Slave Response
Byte
Slave Address
Byte
Function Code (06)
Bytes
Register Address
Bytes
Register Value
Bytes
CRC Checksum
Length
1
Byte
1
Byte
1
Byte
2
Bytes
2
Bytes
2
Bytes
Length
1
Byte
1
Byte
2
Bytes
2
Bytes
2
Bytes
nd
deceleration
www.microlectra.nl

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Eco Optidrive Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Odv-3-220043-1f12-snOdv-3-220070-1f12-snOdv-3-220105-1f12-snOdv-3-220105-3f12-snOdv-3-220043-3f12-snOdv-3-220070-3f12-sn ... Show all

Table of Contents