This Document is for use with version 3.05 Firmware. Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any contract.
Optidrive E3 Advanced Technical Manual Issue 05.Docx 2 Optidrive E3 Parameter Set Overview About this section This document provides a list of the available parameters, and a description of their respective functions, for the Optidrive E3. Parameter Structure Overview and Access The parameter set is arranged in Groups according to the following structure:- Parameter Group Range...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Parameter Descriptions 2.3.1 Basic Parameters Par. Description Minimum Maximum Default Units P-01 Maximum Frequency / Speed Limit P-02 500.0 50.0 (60.0) Hz / RPM Maximum output frequency or motor speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM The maximum possible value is limited by the lower of the following :- 500.0Hz maximum limit P-09 x 5...
Page 7
Optidrive E3 Advanced Technical Manual Issue 05.Docx Par. Description Minimum Maximum Default Units Drive P-11 Low Frequency Torque Boost Current Dependent Low Frequency Torque Boost is used to increase the applied motor voltage and hence current at low output frequencies. This can improve low speed and starting torque.
Page 8
Optidrive E3 Advanced Technical Manual Issue 05.Docx 2.3.2 Extended parameters Par. Description Minimum Maximum Default Units P-15 Digital Input Function Select Defines the function of the digital inputs depending on the control mode setting in P-12. See section 2.6 Control Terminal Connections for more information.
Page 9
Optidrive E3 Advanced Technical Manual Issue 05.Docx Par. Description Minimum Maximum Default Units P-26 Skip frequency hysteresis band P-01 Hz / RPM P-27 Skip Frequency Centre Point P-01 Hz / RPM The Skip Frequency function is used to avoid the Optidrive operating at a certain output frequency, for example at a frequency which causes mechanical resonance in a particular machine.
Page 10
Optidrive E3 Advanced Technical Manual Issue 05.Docx Par. Description Minimum Maximum Default Units P-33 Spin Start (S2 & S3 Only) / DC Injection Time On Start (S1 Only) Setting Function Description Disabled Enabled When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control the motor from its current speed.
Page 11
Optidrive E3 Advanced Technical Manual Issue 05.Docx Par. Description Minimum Maximum Default Units P-43 PI Controller Operating Mode Setting Function Description Direct Operation Use this mode if when the feedback signal drops, the motor speed should increase. When the drive restarts following standby, the PID controller will restart from zero. Inverse Operation Use this mode if when the feedback signal drops, the motor speed should decrease.
Page 12
Optidrive E3 Advanced Technical Manual Issue 05.Docx 2.3.3 Advanced Parameters Par. Description Minimum Maximum Default Units P-51 Motor Control Mode Setting Control Method Vector speed control mode for Induction Motors V/f mode for Induction Motors PM vector speed control for Permanent Magnet Motors BLDC vector speed control for Brushless DC Motors SR vector speed control for Synchronous Reluctance Motors LSPM vector speed control for Line Start Permanent Magnet Motors...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Alternative Parameter Functions for Single Phase Output Drives Single phase output drives feature a number of changes in order to provide optimal operation with single phase motors. These changes are based around two key principles:- ...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Parameter Group 0 – Monitoring Parameters (Read Only) Par. Description Explanation P00-01 1 Analog input value (%) 100% = max input voltage P00-02 2 Analog input value (%) 100% = max input voltage P00-03 Speed reference input (Hz / RPM) Displayed in Hz if P-10 = 0, otherwise RPM P00-04 Digital input status...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Control Terminal Connections For standard applications and operation, the basic control of the drive and functions of all drive input terminals can be configured using just two parameters, P-12 and P-15. P-12 is used to define the source of all control commands and the primary speed reference source. P-15 then allows fast selection of Analog and Digital Input functions based on a selection table.
Page 16
Optidrive E3 Advanced Technical Manual Issue 05.Docx 2.6.2 Overview Optidrive E3 uses a Macro approach to simplify the configuration of the Analog and Digital Inputs. There are two key parameters which determine the input functions and drive behaviour:- P-12 – Selects the main drive control source and determines how the output frequency of the drive is primarily controlled. ...
Optidrive E3 includes an embedded function to allow the user to create their own “default” parameters. This means that if a factory reset is carried out, the drive will return to these parameters, as opposed to the Invertek Drive factory default parameters. This feature is accessed using Optitools Studio PC software only, which may be freely downloaded from the Invertek Drives website. 2.7.2.1 Creating the default parameter set In order to create the User Default settings, the following process should be used.
Page 21
Optidrive E3 Advanced Technical Manual Issue 05.Docx Make any changes to the parameter set as required. Changes from Invertek factory default settings are highlighted in blue. In the File menu, select “Save Current Parameters as User Defaults in Drive” 22 / 69...
Page 22
Optidrive E3 Advanced Technical Manual Issue 05.Docx The confirmation message will appear. 2.7.2.2 Clearing User Default Parameters In order to clear the User Default parameters, the following method is used. From the File menu, select “Clear User Default Parameters in Drive” 23 / 69...
Optidrive E3 Advanced Technical Manual Issue 05.Docx The confirmation message will appear to show the user defaults are now cleared, and resetting the drive will return it to Invertek Drives Factory default settings. 2.7.3 Automatic Switching Frequency Reduction 2.7.3.1 Heatsink Temperature Based Effective Switching Frequency Reduction When the drive heatsink temperature exceeds preset threshold values, the output Effective Switching Frequency is automatically reduced below the value selected in P-17 to reduce the risk of over temperature trip.
Page 24
Optidrive E3 Advanced Technical Manual Issue 05.Docx 2.8.2 LED Display Meanings LED Segments Behaviour Meaning a,b,c,d,e,f Flashing all together Overload, motor output current exceeds P-08 a and f Flashing alternately Mains Loss (Incoming AC power has been removed) Flashing Fire Mode Active 25 / 69...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 4 Fieldbus Interface Support Fieldbus Support Overview Optidrive E3 provides support for the following fieldbus networks and functions Fieldbus Interface Drive Control Drive Parameter Access Modbus RTU On-board RJ45 Access to all Writable Parameters CAN bus On-board RJ45 Access to all Writable Parameters...
Page 28
Optidrive E3 Advanced Technical Manual Issue 05.Docx Customer configuration (mapping) will NOT be saved during power down. This means that the CANopen configuration will restore to its default condition each time the drive is powered up. 4.5.2 PDO Default Mapping Objects Mapped Length...
Page 29
Optidrive E3 Advanced Technical Manual Issue 05.Docx 4.5.4 CAN Open Specific Object Table Index Function Access Type Default Value Index 1000h Device Type 1001h Error Register 1002h Manufacturer Status Register 1005h COB-ID Sync 00000080h 1008h Manufacturer Device Name String ODE3 1009h Manufacturer Hardware Version String...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Parameter Access Overview The accessible parameter numbers and respective scaling are listed in the following tables. The method to access the parameters depends on the fieldbus type in use as described in the following section. The R/W column indicates whether the values are Writeable as well as readable (R/W) or Read Only (R) The data types for the parameter are defined as follows:- WORD...
Page 31
Optidrive E3 Advanced Technical Manual Issue 05.Docx Modbus Parameter Upper byte Lower Byte Format Type Scaling Open Index Number Register Index 27D6h P00-13 Trip 1 Time – Hours 65535 1 = 1 Hour 26D7h P00-13 Trip 1 Time - Seconds 3599 100 = 100 Seconds 27D8h...
Page 32
Optidrive E3 Advanced Technical Manual Issue 05.Docx 4.6.2 Modbus RTU / CAN Open Index – Parameters Modbus Open Par. Description Format Data format / scaling Register Index 2065h Max speed limit 5*P-09 Internal value (3000 = 50.0Hz) 2066h Min speed limit P-01 Internal value (3000 = 50.0Hz) 2067h...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Modbus Open Par. Description Format Data format / scaling Register Index 2090h User PI reference select See parameter description for details 2091h User PI digital reference 1000 1dp, e.g. 100 =10.0% 2092h User PI feedback select See parameter description for details 2093h 0: 0...10V...
Page 34
Optidrive E3 Advanced Technical Manual Issue 05.Docx 4.7.5 Drive status and error code Word High byte gives drive error code. (Valid when the drive is tripped, see 0 for further details) Low byte gives drive status information as follows:- Bit 0: 0 =Drive Stopped, 1 = Drive Running Bit 1: 0 = OK, 1 = Drive Tripped Bit 5: 0 = OK, 1 = In Standby Mode Bit 6: 0 = Not Ready, 1 = Drive Ready to Run (not tripped, hardware enabled and no mains loss condition)
Optidrive E3 Advanced Technical Manual Issue 05.Docx 4.7.11 Display Scaling (P-40) The parameter value is stored as a combined 16 bit word which is constructed as follows:- High Byte Low Byte Display Scaling Source Display Scaling Factor: 3dp, e.g. 0 – 16000 = 0.000 – 16.000 0: Motor Speed 1: Motor Current 2: Analog Input 2 Signal...
For a network with multiple drives, refer to „Multi Drive Network Example“ on page 38 Gateways supplied by Invertek drives are pre-configured to operate with 4 connected E3 drives, unless an alternative number is specified when ordering. ...
The drive sub network connects to the connector on the bottom of the gateway, using the supplied DB9-RJ45 cable. For a single drive installation, the cable can be connected directly from the gateway to the Optidrive. For a network of multiple drives, the network can be easily constructed using suitable RJ45 cables and splitters available from your Invertek Drives Sales Partner. 5.4.1 Single Drive Network Example The gateway is connected to the drive using the supplied Blue Male DB9-RJ45 Subnetwork Connection Cable.
Optidrive E3 Advanced Technical Manual Issue 05.Docx Commissioning Drive Parameter Settings 5.5.1 P-36 Communication Configuration The Optidrive communication parameters are set using P-36, which has three indices as follows:- P-36 Serial Communications Configuration Index 1 : Address Range : 0 – 63, default : 1 For a single drive network, the address must be set to 1.
Optidrive E3 Advanced Technical Manual Issue 05.Docx Gateway Memory Mapping The PLC programmer can read/write the PLC memory mapping to gateway memory in order to monitor/control drives in the sub network. 5.6.1 Input memory This part of the memory contains the real-time drive information that can be read by the PLC. Start Data Data...
Page 40
Optidrive E3 Advanced Technical Manual Issue 05.Docx 5.6.2 Output memory This part of the memory contains the control command information to allow the PLC to control the drives. Start Data Data Drive Data Unit Description Address Length Range Control command 0x0200 16 bits Refer to Drive Control Word on page 41...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Drive status and error code Word on page 35. Controlling the Optidrive(s) The following points should be noted when attempting to control the Optidrive(s):- The drive must be set for Modbus RTU control using P-12 ...
Optidrive E3 Advanced Technical Manual Issue 05.Docx Profibus DP Gateway Features – OD-PROFB-IN Complete PROFIBUS-DP slave functionality according to IEC 61158 Supports all common baud rates up to 12 Mbit (detected automatically) Up to 64 bytes of I/O data in each direction, allowing up to 8 Optidrives to be connected to a single gateway. ...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 5.10 Diagnostics and Troubleshooting Symptom Suggested Actions No Communication, Check all network cables Master > Gateway Check correct bus termination Check correct node address on gateway Check GSD / EDS file is recognised and used by the Master Check the Status LEDs 1 and 2 Profibus Communication Check the subnetwork Status LED...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 6 Diagnostic and Fault Messages Fault Messages Fault Description Code no-Flt No Fault OI-b 01 Brake channel over current OL-br 02 Brake resistor overload 03 Instantaneous over current I.t-trp 04 Motor Thermal Overload (I2t) O-Volt 06 Over voltage on DC bus U-Volt...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 7 Rated Temperatures and De-rating curves Thermal Management The Optidrive E3 product range has an integrated Thermal Management function. This function allows the drive to automatically reduce the drive output switching frequency when operating at higher heatsink temperatures to avoid the risk of an over temperature trip. The table below shows the heatsink temperature threshold points at which thermal management occurs.
Optidrive E3 Advanced Technical Manual Issue 05.Docx 8 Immunity Tests Electrostatic Discharge (ESD) The Optidrive E3 product range has been designed and tested to comply with the limits defined in EN 61800-3:2004+A1-2012. The test techniques used are as defined in EN 61000-4-2:2009. Application Test points Test Method...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 9 General Technical and Performance Data Electrical Data 9.1.1 Mains Supply Details Supply Voltage Range 110 Volt Units – 110 – 115 Volt +10% / -10% 230 Volt Units – 200 – 240 Volt +10% / -10% 400 Volt Units –...
Optidrive E3 Advanced Technical Manual Issue 05.Docx DC Bus Discharge Time DC Bus discharge times are based on maximum continuous rated DC bus voltage. In compliance with EN 61800-5-1:2007, all drives have a caution on the rating labels stating “Power down for 5 minutes before removing cover” DC Bus Voltage Time to Frame...
Optidrive E3 Advanced Technical Manual Issue 05.Docx 9.10.2 Overview Optidrive E3 features both hardware and software protection of the output stage to prevent damage. In addition, an Ixt system is used to monitor motor overload condition and prevent damage to the motor due to operation for prolonged periods at high load. I x t protection is software based, using the value for motor rated current programmed in P-08.