9. Digital Input Functions
9.1. Digital Input Configuration Parameter P1-13
P1-13
Local (Hand)
Digital Input 1
*(2)
Control Function
N/A
All functions User defined in Menu 9 or configured through PLC function in OptiTools studio software
0
suite.
O: Stop
*(3)
1
C: Run / Enable
O: No Function
2
Analog Input 2
C: Momentary Start
O: Stop
3
C: Run / Enable
O: Stop
4
C: Run / Enable
O: Stop
5
C: Run / Enable
O: No Function
6
Preset Speeds
C: Momentary Start
O: Stop
7
C: Run / Enable
O: Stop
8
C: Run / Enable
O: Stop
*(3)
9
C: Run / Enable
O: Stop
*(3)
Keypad Speed
10
C: Run / Enable
Reference
O: No Function
11
C: Momentary Start
O: Stop
12
C: Run Fwd
O: Stop
13
C: Run Fwd
O: Stop
14
C: Run
Notes
*(1): Logic shown is as per the default setting. Fire mode logic can be configured through parameter P8-09.
*(2): Default setting for P1-13 = 1
*(3): When the drive is in PID control (P1-12 = 3) and digital preset reference is selected (P3-05 = 0) then P1-13 can be set to 1, 9, or 10 to
allow selection between two independent digital references using digital input 2. Digital preset reference 1 and 2 are set in P3-06 and
P3-15 respectively.
Note,"Motor,thermistor,trip",connection,is,via analog input 2 and is configured by parameter P2-33
longer utilised for the thermistor input (this is different to the ODP drive and E2 drive).
www.microlectra.nl
Optidrive Eco User Guide Revision 2.01
Digital Input 2
(Terminal 2)
(Terminal 3)
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Stop (Disable)
C: Run Permit
O: Forward
C: Reverse
O: Fire Mode
*(1)
C: Normal Operation
O: Preset Speed 1
C: Preset Speed 2
O: Stop (Disable)
C: Run Permit
O: Forward
C: Reverse
O: Fire Mode
*(1)
C: Normal Operation
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Normal Operation
C: Preset 1 / PI Set-point
2
O: Stop (Disable)
C: Run Permit
O: Forward
C: Reverse
O: Fire Mode
*(1)
C: Normal Operation
O: Forward
C: Reverse
Digital Input 3
Analog Input 1
(Terminal 4)
(Terminal 6)
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
* (1)
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
* (1)
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
C: Local Ctrl
O: Remote Ctrl
Analog In 1
* (1)
C: Local Ctrl
Digital input 3
Analog input 1
Analog input 2
Off
Off
On
Off
Off
On
On
On
Off
Off
On
Off
Off
On
On
On
Analog Input 2
(Terminal 10)
When Input 3 is
Analog In 2
Closed:
Speed Reference =
Analog Input 2
Analog In 2
Start Command =
Input 1
Analog In 2
In PI Mode, Analog
Input 1 must be used
Analog In 2
for feedback
O: Ext Trip
When Input 3 is
C: Normal Operation
Closed:
O: Preset 1
Speed Reference =
Preset Speed 1 / 2
C:Preset 2l
Start Command =
O: Preset 1
Input 1
C:Preset 2
O: Preset 1
C:Preset 2
When Input 3 is
Analog In 2
Closed:
Speed Reference =
Keypad
O: Ext Trip
Start Command =
C: Normal Operation
Determined by P2-37
Analog In 2
Analog In 2
Analog In 2
Preset Speed
Off
Preset Speed 1
Off
Preset Speed 2
Off
Preset Speed 3
Off
Preset Speed 4
On
Preset Speed 5
On
Preset Speed 6
On
Preset Speed 7
On
Preset Speed 8
(
),The,"External,trip",input,is no
Notes
29