Planning the use

3.3 Ambient conditions for operation

Test
Vibration, sinusoidal as per
IEC 60068-2-6:2007
Test Fc
Shock
as per IEC 60068-2-27:2008
Test Ea
NOTICE
Equipment failure
Moisture and condensation lead to malfunction. Moisture in the form of condensation on or
in the device is formed:
 When transporting a device at low temperatures
 Under extreme temperature variations
Bring the device to room temperature before operating.
Condensation
When condensation is on the device, do not expose the HMI device to direct radiation from
a heater.
If condensation has developed, wait approximately 4 hours until the HMI device has dried
completely before switching it on.
The following points must be adhered to in order to ensure a fault-free and safe operation of
the HMI device:
● Proper transportation and storage
● Proper installation and mounting
● Careful operation and maintenance
The warranty for the HMI device will be deemed void if these stipulations are not heeded.
3.3
Ambient conditions for operation
Mechanical and climatic ambient conditions
The HMI device is designed for use in a location protected from the effects of the weather.
The ambient conditions meet the requirements for IEC 60721-3-3 Edition 2.2:2002:
● Mechanical requirements according to class 3M3
● Climatic requirements according to class 3K3
30
Permitted range
5 to 8 Hz, 3.5 mm, 10 cycles per axis
8 to 500 Hz, 9.8 m/s
, 10 cycles per axis
2
250 m/s
, 6 ms, 1000 shocks
2
Operating Instructions, 10/2010, A5E03284305-01
KP8, KP8F