Setting the KP8 and KP8F
6.3 Setting controller - communication HMI device
Procedure – Setting slot 1
1. Double click in the properties window on slot 1.
2. Open the "Addresses" tab.
3. Change the entries, if required.
4. Select the "Parameters" tab.
5. Open the "Parameters > Device-specific parameters" folder.
60
The "Properties – KP8 inputs/outputs" dialog box opens.
In the "Inputs" and "Outputs" groups, the start values of the address areas are set
depending on the controller used.
Parameter
Inputs > Start
Inputs > Process Image
Outputs > Start
Outputs > Process Image
Parameter
Duration of the light test
Brightness
Function of the clamp 0
Function of the clamp 1
Function of the clamp 2
Function of the clamp 3
Function of the clamp 4
Function of the clamp 5
Function of the clamp 6
Function of the clamp 7
Meaning
Start of address range in which the PROFIsafe inputs/outputs for
the fail-safe HMI device are mapped.
Process image to which the address range belongs.
This parameter cannot be set with controllers of the
SIMATIC CPU 300 type.
Start of address range in which the PROFIsafe inputs/outputs for
the fail-safe HMI device are mapped.
Process image to which the address range belongs.
This parameter cannot be set with controllers of the
SIMATIC CPU 300 type.
Meaning
The value range from 0 to 60 s can be set.
With the value "0", no light test is executed.
Default setting is 5 s.
Adjustable:
very bright, bright, normal, dark or very dark
Default setting is "normal".
Adjustable:
Input or output, default setting is input
Adjustable:
Input or output, default setting is input
Adjustable:
Input or output, default setting is input
Adjustable:
Input or output, default setting is input
Adjustable:
Input or output, default setting is output
Adjustable:
Input or output, default setting is output
Adjustable:
Input or output, default setting is output
Adjustable:
Input or output, default setting is output