Input unit – 1oo2 mode
Parameter
Hardware Fault Tolerance
Classification
Architecture
Failure mode
Failure Mode Diagnostic
Diagnostic Coverage
Diagnostic test interval
Safe Failure Fraction
Common Cause Factor
Controller
Parameter
Hardware Fault Tolerance
Classification
Architecture
Failure mode
Failure Mode Diagnostic
Diagnostic Coverage
Diagnostic test interval
Safe Failure Fraction
Common Cause Factor
KP8, KP8F
Operating Instructions, 10/2010, A5E03284305-01
Detected
Undetected
Detected
Undetected
detected
undetected
Detected
Undetected
Value
1
A
1oo2D
Dangerous process value
5.78 FIT
0.06 FIT
No error signaling or no safe
values
0 FIT
0 FIT
99.00 %
15 ms
99.86 %
2 %
Value
1
B
1oo2D
Dangerous process value
174,00 FIT
1,68 FIT
No error signaling or no safe
values
0 FIT
0 FIT
99.04 %
15 ms
99.23 %
2 %
Technical specifications
9.3 Fail-safe mode
Comment
1st detected failure leads to the safe
state
Due to failures in the input circuit
One channel
One channel
Calculation according
IEC13849:2006 CAT4
Errors detected in each firmware
cycle
Comment
1st detected failure leads to the safe
state
Due to failures in the processing unit
One channel
One channel
Calculation according
IEC13849:2006 CAT4
Errors detected in each firmware
cycle