Setting the KP8 and KP8F
6.4 Configuring Media Redundancy Protocol
Procedure
1. Double-click the "X2" slot in the station window.
2. Select the "Media Redundancy" tab.
3. Select "Manager (Auto)".
4. Click "OK".
5. Select KP8 again in the station window.
62
The following dialog appears.
The "X317-2" controller can perform three different roles in MRP.
Parameter
Not in the ring
Manager (Auto)
Client
The entry is saved. The dialog box closes.
Meaning
The "X317-2" controller is not a node of the MRP
The "X317-2" controller is the Manager of the MRP
The "X317-2" controller is the Client of the MRP