5. How to Install

5.3. Final Set-Up and Test

5.3.1. Final Set-Up and Test
To test the set-up and ensure that the frequency converter is running, follow these steps.
Step 1. Locate the motor name plate
Step 2. Enter the motor name plate data in this parameter list.
To access this list first press the [QUICK MENU] key then select "Q2 Quick
5
Setup".
1.
Motor Power [kW]
or Motor Power [HP]
2.
Motor Voltage
3.
Motor Frequency
4.
Motor Current
5.
Motor Nominal Speed
Step 3. Activate the Automatic Motor Adaptation (AMA)
Performing an AMA will ensure optimum performance. The AMA measures the values from the motor model equivalent diagram.
1.
Connect terminal 27 to terminal 12 or set par. 5-12 to 'No function' (par. 5-12 [0])
2.
Activate the AMA par. 1-29.
3.
Choose between complete or reduced AMA. If an LC filter is mounted, run only the reduced AMA, or remove the LC filter during the AMA
procedure.
4.
Press the [OK] key. The display shows "Press [Hand on] to start".
5.
Press the [Hand on] key. A progress bar indicates if the AMA is in progress.
104
par. 1-20
par. 1-21
par. 1-22
par. 1-23
par. 1-24
par. 1-25
MG.11.B7.02 - VLT
®
VLT
NB!
The motor is either star- (Y) or delta- connected (Δ).
This information is located on the motor name plate
data.
is a registered Danfoss trademark
®
HVAC Drive Design Guide