5. How to Install
Frequency
Bussmann
converter
UL Compliance - 380-480 V, 525-600 V
kW
Type RK1
K37-1K1
KTS-R6
1K5-2K2
KTS-R10
3K0
KTS-R15
4K0
KTS-R20
5K5
KTS-R25
7K5
KTS-R30
11K
KTS-R40
15K
KTS-R40
18K
KTS-R50
22K
KTS-R60
30K
KTS-R80
37K
KTS-R100
45K
KTS-R125
55K
KTS-R150
75K
FWH-220
90K
FWH-250
5
Table 5.12: UL fuses 380 - 600 V
KTS-fuses from Bussmann may substitute KTN for 240 V frequency converters.
FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V frequency converters.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V frequency converters.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V frequency converters.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V frequency converters.
High Power Fuse Tables
Bussmann
Size/
E1958
Type
JFHR2**
P110
FWH-
300
P132
FWH-
350
P160
FWH-
400
P200
FWH-
500
P250
FWH-
600
Table 5.14: D enclosures, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL requirements.
Size/Type
P110
P132
P160
P200
P250
P315
Table 5.15: D enclosures, 525-600 V
Size/Type
P315
P355
P400
P450
Table 5.17: E enclosures, 380-480 V
98
Bussmann
Bussmann
Type J
Type T
JKS-6
JJS-6
JKS-10
JJS-10
JKS-15
JJS-15
JKS-20
JJS-20
JKS-25
JJS-25
JKS-30
JJS-30
JKS-40
JJS-40
JKS-40
JJS-40
JKS-50
JJS-50
JKS-60
JJS-60
JKS-80
JJS-80
JKS-100
JJS-100
JKS-150
JJS-150
JKS-150
JJS-150
-
-
-
-
Bussmann
SIBA
E4273
E180276
T/JDDZ**
RKI/JDDZ
JJS-
2028220-
300
315
JJS-
2028220-
350
315
JJS-
206xx32-
400
400
JJS-
206xx32-
500
500
JJS-
206xx32-
600
600
Bussmann
E125085
Amps
JFHR2
170M3017
315
170M3018
350
170M4011
350
170M4012
400
170M4014
500
170M5011
550
Bussmann PN*
Danfoss PN
170M5013
20221
170M6013
20221
170M6013
20221
170M6013
20221
MG.11.B7.02 - VLT
SIBA
Littel fuse
Type RK1
Type RK1
5017906-006
KLS-R6
5017906-010
KLS-R10
5017906-016
KLS-R16
5017906-020
KLS-R20
5017906-025
KLS-R25
5012406-032
KLS-R30
5014006-040
KLS-R40
5014006-040
KLS-R40
5014006-050
KLS-R50
5014006-063
KLS-R60
2028220-100
KLS-R80
2028220-125
KLS-R100
2028220-125
KLS-R125
2028220-160
KLS-R150
2028220-200
L50S-225
2028220-250
L50S-250
Ferraz-
LittelFuse
Bussmann
Shawmut
E71611
E4274
E60314
JFHR2**
H/JDDZ**
JFHR2**
L50S-300
A50-P300
NOS-
L50S-350
A50-P350
NOS-
L50S-400
A50-P400
NOS-
L50S-500
A50-P500
NOS-
L50S-600
A50-P600
NOS-
SIBA
E180276
JFHR2
2061032.315
2061032.350
2061032.350
2061032.400
2061032.500
2062032.550
Rating
900 A, 700 V
900 A, 700 V
900 A, 700 V
900A, 700 V
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Design Guide
Ferraz-
Ferraz-
Shawmut
Shawmut
Type CC
Type RK1
ATM-R6
A6K-6R
ATM-R10
A6K-10R
ATM-R16
A6K-16R
ATM-R20
A6K-20R
ATM-R25
A6K-25R
ATM-R30
A6K-30R
-
A6K-40R
-
A6K-40R
-
A6K-50R
-
A6K-60R
-
A6K-80R
A6K-100R
A6K-125R
A6K-150R
A50-P225
A50-P250
Bussmann
Internal
E125085
Option
JFHR2*
Bussmann
170M3017
170M3018
300
170M3018
170M4016
350
170M4012
170M4016
400
170M4014
170M4016
500
170M4016
170M4016
600
Ferraz-Shawmut
E76491
JFHR2
6.6URD30D08A0315
6.6URD30D08A0350
6.6URD30D08A0350
6.6URD30D08A0400
6.6URD30D08A0500
6.6URD32D08A0550
Losses (W)
120
120
120
120