7. RS-485 Installation and Set-up
Text block:
The text block is used to read or write texts via the data block.
7.4.7. The PKE Field
The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU:
7
Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Parameter commands master ⇒ slave
Bit no.
15
14
0
0
0
0
0
0
0
0
1
1
1
1
1
1
Response slave ⇒master
Bit no.
15
14
0
0
0
0
0
0
0
1
1
1
132
Parameter command
13
12
0
0
No command
0
1
Read parameter value
1
0
Write parameter value in RAM (word)
1
1
Write parameter value in RAM (double word)
0
1
Write parameter value in RAM and EEprom (double word)
1
0
Write parameter value in RAM and EEprom (word)
1
1
Read/write text
Response
13
12
0
0
No response
0
1
Parameter value transferred (word)
1
0
Parameter value transferred (double word)
1
1
Command cannot be performed
1
1
text transferred
MG.11.B7.02 - VLT
®
is a registered Danfoss trademark
®
VLT
HVAC Drive Design Guide