HVAC Drive Design Guide
Size/Type
P355
P400
P450
P500
P560
Table 5.18: E enclosures, 525-600 V
*170M fuses from Bussmann shown, use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
*170M fuses from Bussmann shown, use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage
may be substituted for external use.
5.2.21. Access to Control Terminals
All terminals to the control cables are located underneath the terminal cover on the front of the frequency converter. Remove the terminal cover by means
of a screwdriver (see illustration).
Illustration 5.31: A1, A2, A3,B3, B4, C3 and C4 enclosures
5.2.22. Control Terminals
Drawing reference numbers:
1.
10 pole plug digital I/O.
2.
3 pole plug RS485 Bus.
3.
6 pole analog I/O.
4.
USB Connection.
Bussmann JFHR2*
170M5013/170M4017
170M5013/170M4017
170M6013
170M6013
170M6013
MG.11.B7.02 - VLT
®
is a registered Danfoss trademark
SIBA Type RK1
FERRAZ-SHAWMUT Type RK1
2061032.700
2061032.700
2063032.900
2063032.900
2063032.900
Illustration 5.32: A5, B1, B2, C1 and C2 enclosures
5. How to Install
900 A, 700 V
900 A, 700 V
900 A, 700 V
900A, 700 V