VLT
HVAC Drive Design Guide
5. How to Install
5
Illustration 5.50: EMC-correct electrical installation of a frequency converter in cabinet.
5.7.2. Use of EMC-Correct Cables
Danfoss recommends braided screened/armoured cables to optimise EMC immunity of the control cables and the EMC emission from the motor cables.
The ability of a cable to reduce the in- and outgoing radiation of electric noise depends on the transfer impedance (Z
). The screen of a cable is normally
T
designed to reduce the transfer of electric noise; however, a screen with a lower transfer impedance (Z
) value is more effective than a screen with a
T
higher transfer impedance (Z
).
T
Transfer impedance (Z
) is rarely stated by cable manufacturers but it is often possible to estimate transfer impedance (Z
) by assessing the physical
T
T
design of the cable.