Setting The Basic Parameters - Siemens SITRANS F MAG 8000 Standard Operating Instructions Manual

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F MAG 8000 Standard:
Table of Contents

Advertisement

Commissioning

6.3 Setting the basic parameters

6.3
Setting the basic parameters
Note
No factory reset
The device is delivered with factory settings that are not stored as default values. Because no
default values are present in the meter, an automatic return to factory values is not possible.
Enter password
The "User" dialog box is always displayed on the first start-up after installation of SIMATIC
PDM but not on the first start-up for a specific device.
You can also use the menu command "Options" → "Settings" to specify whether you are
permanently registered as a "Maintenance engineer" or "Specialist" and/or whether to disable
the display of the "User" dialog box. Refer to SIMATIC PDM help manual for more details of
"Maintenance engineer" and "Specialist".
Proceed as follows:
Click the appropriate button ("Maintenance engineer" or "Specialist").
If the option "Specialist" is selected, enter the password in the "Password" box in order to work
with additional parameters. The default password is "1000", and can be changed after gaining
access to the meter.