Troubleshooting/FAQs
9.1
Fault codes
Error system
MAG 8000 can detect and report 14 different faults.
The faults are divided into two types: Fatal errors and Warnings.
Fatal errors: Faults 1, 2, 3, and 4
Warnings: Faults 5, 6, 7, 8, 9, L, E, C, d, and 14
Fault
Name/text
codes
1
Insulation fault "Cross-talk" between
2
Coil current
fault
3
Amplifier over‐
load
SITRANS MAG 8000
Operating Instructions, 11/2018, A5E03071515-AE
Description
coil circuit and electro‐
des. An insulation fault
will result in a offset er‐
ror on flow measure‐
ment
(Advanced version on‐
ly)
Error in the coil circuit.
Coil current has not set‐
tled within specified pe‐
riod.
A short-circuit in the coil
can NOT be detected
Input signal is outside
expected range.
Input amplifier circuit
can not provide a stable
measurement.
A short circuit between
the two electrodes or
between a electrode
and common can NOT
be detected
Cause
● Defect cables between
sensor and transmitter
● Wrong connections of
remote cables
● Water between coils
and electrodes – could
be caused by a broken
liner
● Pollution/moisture on
PCB caused by water in
encapsulation
● Coils have been
disconnected could be
caused by broken cable
or wires
● Electrodes have been
disconnected, or
connected to ground
Remedy
Check cable and wiring installation and dis‐
turbing elements in the surrounding.
Re-activation of insulation test (parameter
800) will reset alarm and start a new insu‐
lation test.
During the 4 minute insulation test, meas‐
urement is disabled.
Alarm remains active until a new test period
detects no failures.
Check cable and wiring installation.
Alarm remains active until the fault condi‐
tion is corrected.
Check cable and wiring installation.
Alarm remains active until the fault condi‐
tion is corrected.