Siemens SITRANS F MAG 8000 Standard Operating Instructions Manual page 143

Electromagnetic flowmeters
Hide thumbs Also See for SITRANS F MAG 8000 Standard:
Table of Contents

Advertisement

Param‐
Meter
Display
eter ID
version
view
323
All
-
324
All
-
325
All
-
327
All
-
328
All
-
329
All
-
331
All
-
332
All
-
333
All
-
334
All
-
Table C-1
Sensor size
DN 25 (1")
DN 40 (1½")
DN 50 (2")
SITRANS MAG 8000
Operating Instructions, 11/2018, A5E03071515-AE
Parameter/data type
Calibration factor
Gain correction
Sensor offset
Adjustment Factor
Low flow cut-off
Filter time constant
Excitation frequency limit
Excitation frequency sensor
limit
Empty pipe detection ena‐
ble
Empty pipe limit
MAG 8000 Standard (7ME6810) parameter 328 FW 3.09
Parameter value
0.16
0.15
0.17
Factory settings
Fixed parameter or meter data that are not changeable
Sensor-related
Sensor-related
Sensor-related
1
MAG 8000 Standard
(7ME6810) 0.05 % for
FW 3.07 and lower. For
FW 3.09 see table C1
MAG 8000 Standard pa‐
rameter 328 FW 3.09 be‐
low.
MAG 8000 CT
(7ME6820) 0.25 % for
FW 3.07 and lower. For
FW 3.09 see table C2
MAG 8000 CT parame‐
ter 328 FW 3.09 below.
MAG 8000 Irrigation
(7ME6880) 1 %
5 Tau
6.25 Hz for advanced
version and 1/15 Hz for
basic version
Sensor-related
Yes
25000 ohm
C.2 Parameter lists
Data range
-2 to 2
0 to 9.9%
1 to 1000
7ME6810 and 7ME6820:
6.25 Hz
(DN 25 to 200 (1" to 8"))
3.125 Hz
(DN 250 to 600 (10" to 24"))
1.5625 Hz
(DN 700 to 1200 (28" to 48"))
7ME6880:
3.125 Hz
(DN 25 to 600 (1" to 24"))
1.5625 Hz
(DN 700 to 1200 (28" to 48"))
Yes / No
0 to 2.15x10
9