Step 2: Pairing Power Optimizers To The Inverter - SolarEdge SE3000H-US Installation Manual

Single phase inverter with hd-wave technology
Hide thumbs Also See for SE3000H-US:
Table of Contents

Advertisement

Step 2: Pairing Power Optimizers to the Inverter

Step 2: Pairing Power Optimizers to the Inverter
Once all connections are made, all the power optimizers must be logically paired to their inverter. The 
power optimizers do not start producing power until they are paired. This step describes how to assign 
each inverter to the power optimizers from which it will produce power.
Perform this step when the modules are exposed to sunlight. If the string length is changed or a power 
optimizer is replaced, repeat the pairing process.
 1.  Perform pairing: Press and hold down the inverter LCD OK button for about 10 seconds. The 
following message is displayed: 
K e e p
f o r
p a i r i n g ,
t o
e n t e r
R e m a i n i n g :
Keep holding for 5 seconds until the following is displayed:
P a i r i n g
T u r n
 2.  Turn the inverter ON/OFF switch to ON within 5 seconds. If you wait longer than 5 seconds the 
inverter exits the pairing mode. The following message is displayed indicating that the inverter is 
performing the pairing:
P a i r i n g
R e m a i n i n g
 3.  Wait for the completion of the pairing (remaining seconds is 0). If pairing fails, an error is displayed. In 
this case, repeat the pairing steps, and refer to Power Optimizer Troubleshooting  on page 68. If the 
problem persists, contact SolarEdge Support. When pairing succeeds, the following message is 
displayed:
P a i r i n g
P a i r i n g
The system startup process begins:
Since the inverter is ON, the power optimizers start producing power and the inverter starts converting 
AC.
WARNING!
When you turn ON the inverter ON/OFF switch, the DC cables carry a high voltage and the power 
optimizers no longer output a safe 1V output. 
AVERTISSEMENT!
Après avoir mis l'interrupteur ON/OFF de l'onduleur monophasé sur ON, les câbles DC portent une
haute tension et les optimiseurs de puissance ne génèrent plus la tension de sécurité de 1V.
When the inverter starts converting power after the initial connection to the AC, the inverter enters 
Wakeup mode until its working voltage is reached. This mode is indicated by the flickering green inverter 
LED.
 
34
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
h o l d i n g
b u t t o n
r e l e a s e
m e n u . . .
3
s e c
S w i t c h
T o
O n
[ s e c ] : 1 8 0
C o m p l e t e d

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents