Configuration Menu Options

This section describes how to use the LCD menus for configuring the inverter. 

Country and Grid

 1.  Select the Country option to specify the country or region in which the inverter is installed and the 
grid to which it is connected. This parameter may arrive pre-configured. If so, verify that it is set to 
the proper country or region.
WARNING!
The inverter must be configured to the proper country/ region in order to ensure that it complies with 
the country grid code and functions properly with the country grids.
AVERTISSEMENT!
L'onduleur doit être configuré pour le pays approprié afin d'assurer un fonctionnement convenable
avec le réseau de ce pays.
A list of countries is displayed. If no country is configured, the value is <NONE>.
NOTE
If an inverter is not configured to any country, it will not produce energy, and the following message 
will be displayed on the LCD:
No Country Selected
A plus sign (+) near the country indicates that another menu will be displayed after selection.
 
When selecting Auto , the inverter automatically detects the used grid.
l
 
When selecting an option with No Neutral or No N, connection to Neutral line is not required. 
l
For any other option, you must connect the Neutral line.
 2.  Confirm your country selection in the confirmation screen: Toggle to YES and press Enter.

Language

 1.  Select the Language option to set the language in which the LCD should display.
 2.  Confirm your language selection in the confirmation screen: Toggle to YES and press Enter.

Communication

 1.  Select the Communication option to define and configure:
 
The communication option used by   t he inverter  to communicate with the SolarEdge 
l
monitoring platform 
 
The communication option used to communicate between multiple   S olarEdge devices or 
l
other external non-SolarEdge devices, such as energy meters or loggers.
 2.  Select Server to set which communication method is used to communicate between   d evices and the  
monitoring platform. Refer to Setting Up Communication     on page 52 for a full description of these 
communication options.
NOTE
The Server menu shows only the communication options installed in the inverter.
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
Chapter 5: Configuring the Inverter