Technical Specifications - Single Phase Inverters with HD-Wave Technology (North America)
Recommended OCPD size per grid:
Inverter
Maximum Output Current (A)
SE3000H-US
SE3800H-US
SE5000H-US
SE6000H-US
SE7600H-US
SE10000H-US
SE11400H-US
Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on a single Point of Common Connection.
The default settings are in compliance with IEEE1547. Utility authorization is required to change these set-points.
81
Minimum Fuse Rating (A)
12.5
16
21
25
32
42
47.5
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50%
50 % < V < 88%
110% < V < 120%
V > 120 %
Frequency Range (Hz)
> 60.5
< 59.3 (Hawaii – 57)
Single Phase Inverter with HD-Wave Technology Specifications (North America) MAN-01-00308-1.3
208 VAC
20
20
30
35
40
60
60
0.16
2.00
1.00
0.16
Max. Clearing Time (Sec)
0.16
0.16
Maximum Fuse Rating (A)
240 VAC
---
50
50
50
50
50
---
50
---
50
---
80
---
80