SolarEdge SE3000H-US Installation Manual page 67

Single phase inverter with hd-wave technology
Hide thumbs Also See for SE3000H-US:
Table of Contents

Advertisement

Error Codes
Code
CPU
v3.18xx
CPU v3.19xx
and
and above
below
117
18x75
118
18x76
123
18x7B
127
18x7F
133
18x85
66
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
Error
Message
output. 
 
Refer to the AC Wiring Application Note
o
http://www.solaredge.us/files/pdfs/application-note-
recommended-wiring.pdf
Temperature too high
Overtemp
 
Verify proper inverter clearances. 
o
 
Make sure the heat-sink fins are clean and unobstructed. 
o
Temperature too low
Undertemp
Make sure the inverter is installed in a location with ambient 
temperatures within the range specified in the datasheet.
MainError
Grid measurements are out of range. Contact the grid operator. 
RCD current surge.
Ground faults may occur due to insufficient insulation to the 
ground. 
Only a qualified technician should handle this problem, and only 
IRCDMax
after taking proper precautions.
1. Turn the inverter ON/OFF switch to OFF.
2. Wait five minutes for the input capacitors to discharge.
3. Disconnect the AC breaker.
4. Disconnect the DC inputs.
5. Connect each DC string separately, turn the AC and the 
inverter ON/OFF switch to ON, until the error appears for the 
faulty string.
 
Do not connect strings with a grounding fault to the inverter. 
o
A certified installer must fix the faulty string before 
connecting it to the inverter
 
For further documentation, contact SolarEdge Support.
o
Temp Sensor 
Broken or unconnected temperature sensor. Contact 
SolarEdge Support.
fault
Troubleshooting
WARNING!
ELECTRICAL SHOCK HAZARD. Do 
not touch uninsulated wires when the 
inverter cover is removed. 
AVERTISSEMENT!
RISQUE D'ÉLECTROCUTION, ne
touchez pas les fils non isolés lorsque
le couvercle de l'onduleur est retiré.