 5.  If required, perform any additional connections before closing the inverter cover (for example: 
Communication options connection – refer to Setting Up Communication     on page 52
 6.  Close the inverter cover   b y tightening the screws with a torque of 3.0 N*m/ 2.2 lb*ft. 
 7.  Turn ON the   S afety Switch.   I f an additional external DC switch is installed between the power 
optimizers and the inverter(s) then turn it ON.
A status screen similar to the following appears on the LCD panel:
V a c [ V ]
2 4 0 . 7
P _ O K :
- - - - - - - - - - - - - - -
 8.  Verify that the following information appears on the LCD panel:
 
P_OK: Appears only upon pairing process completion and first telemetry reception from the 
l
power optimizers. Indicates connection to the power optimizers and that at least one power 
optimizer is sending monitoring data. 
 
000/000: Appears only upon first telemetry reception from the power optimizers. Indicates the 
l
number of power optimizers that have been paired to this inverter. 
 
S_OK: the connection to the SolarEdge monitoring platform is successful (should appear only if 
l
the inverter is connected to the server). If S_OK is not displayed and the inverter is connected to 
the server, refer to Errors and Troubleshooting on page 62.
Vac [V]: the grid AC output voltage. Verify the correct value. 
 
l
 
Vdc [V]: The DC input voltage of the longest string connected to the inverter.   T here should be a 
l
safety voltage of 1V for each power optimizer in the string.
NOTE
A measurement error on the inverter  LCD of ±3 V is acceptable.
 
Pac [w]: the AC output power (should be 0.0 since the inverter is OFF). 
l
 
OFF: The inverter ON/OFF switch is in the OFF position. 
l
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
V d c [ V ]
P a c [ w ]
1 4 . 1
0 . 0
0 0 0 / 0 0 0
< S _ O K >
O F F
Chapter 5: Commissioning the Installation
33