Appendix A: Technical Data
A
Technical Data
General
Model name
Order code
Dimensions (L x W x H)
Operating temperature
Storage temperature
Humidity range
Mechanical rating
Mounting
Power supply
Terminal wiring
Certifications
Communication
Interface
Ethernet
IEEE 802.3
Compliance
Protocols
Modbus TCP
(client)
Data rate
10/100 Mbit/s
10BASE-T,
Physical layer
100BASE-TX
Maximum
100 m
cable length
Port connector
Shielded RJ-45
1500 VDC
Isolation
KNX
Order Code
Maximum number of KNX Communication Objects
Maximum number of KNX Main Group Addresses
Maximum number of KNX Associations
Supported Modbus slave device types
Maximum number of Modbus Slave devices
Modbus to KNX Gateway User Manual
Anybus Modbus to KNX Gateway
AB9901-nnnn (nnnn = number of datapoints)
90 x 88 x 56 mm
0 to +60 °C
-40 to +85 °C
5 to 95 % non-condensing
IP20
DIN rail or screw mount
Must be NEC Class 2 or LPS and SELV rated
AC: 24 VAC ±10 %, max. 127 mA
DC: 9 to 36 VDC ±10 %, max. 140 mA
(Recommended: 24 VDC)
Use solid or stranded wires (twisted or with ferrule)
1 core: 0.5 to 2.5 mm
2
2 cores: 0.5 to 1.5 mm
2
3 cores: not permitted
CE and RoHS compliant
See
www.anybus.com/support
KNX TP1 (Port A)
-
KNX
9.6 kbps
KNX TP1, two twisted pairs, overall shield and
sheath
29 VDC / 5 mA
-
2-pin pluggable terminal block
2500 VDC
for more information.
EIA-485 (Port B)
Modbus V1.02
Modbus RTU (master)
2.4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbps
EIA-485, 3-wire isolated
2.4 to 57.6 kbps: 1200 m
115.2 kbps: 1000 m
3-pin pluggable terminal block
1500 VDC (except from D-sub connector)
AB9901 – 100
250
100
250
100
250
200
500
Modbus RTU (EIA485), Modbus TCP
Up to 255 devices per node (RTU and
TCP)
Up to 5 TCP connections
31 (32)
600
1200
3000
600
1200
3000
600
1200
3000
1200
2400
6000
SCM-1202-050 1.2 en-US