Emerson Rosemount 3051 Manual page 43

Transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Figure 3-6. Transducer Block
Properties Window
5. Select the Mode tab.
6. Select Out of Service (OOS) and deselect Auto in the Target Mode
region of the window.
The parameters you change in the properties window remain
highlighted (as in Figure 3-6) so you can easily track changes.
7. Click the Apply button to apply the changes you made.
The software warns you that the changes you made may upset the
process and create a dangerous situation in your plant. Before you
select OK, verify that the control loop is in manual control.
The Actual Mode region changes to OOS.
8.
A warning window will pop up,
Explorer.
9. Right click on the TRANSDUCER block icon to access the
configuration parameters menu.
10. Select the parameter you wish to configure, and follow the on-line
instructions to complete the configuration.
NOTE
As you make changes to the configuration parameters, the software
warns you that the changes you made may upset the process and create
a dangerous situation in your plant. Before you select OK, verify that
the control loop is in manual control.
See "Transducer Block" on page C-1 to change the sensor type and to
calibrate the sensors.
11. Repeat Steps 4 through 8 to return the mode of the transducer
block to Auto.
click OK to return to the DeltaV
Configuration
3-7