This is a short procedure for displaying multiple devices on the Model
3051 transmitters LCD. If a value is brought in from a different device
it must be linked to a block in the Model 3051 transmitter with the
LCD display and it must be downloaded. . The LCD can display up to
four different values. It can display any input or output of any block in
the Model 3051. The first display is pre-configured to show the value of
the transducer block of the Model 3051. The first display may be
changed.
1. Open the LCD block. Select the "Others" tab. Next, scroll down the
list of parameters and select "DISPLAY_PARAM_SEL." A drop
down menu will appear. Select how the ammount of values to be
displayed on the LCD. Next, select the "Write Changes" button.
Figure C-10. Model 3051 Pressure: LCD (TB) Screen
For each value n (n =1 - 4) displayed on the LCD, several parameters must be setup.