Emerson Rosemount 3051 Manual page 105

Transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Table C-5. Resource Block Parameters (continued)
Parameter
security_IO
SHED_RCAS
SHED_ROUT
Simulate_STATE
simulate_IO
RB_SFTWR_REV_ALL
RB_SFTWR_REV_BUILD
RB_SFTWR_REV_MAJOR
RB_SFTWR_REV_MINIOR
start_with_defaults
STRATEGY
ST_REV
summary_status
TAG_DESC
TEST_RW
UPDATE_EVT
WRITE_ALM
WRITE_LOCK
WRITE_PRI
Index
Number
Description
65
Status of security jumper/switch.
26
Time duration at which to give up on computer writes to function block RCas locations.
Shed from RCas shall never happen when SHED_ROUT = 0
27
Time duration at which to give up on computer writes to function block ROut locations.
Shed from ROut shall never happen when SHED_ROUT = 0
66
The state of the simulate jumper.
0 = Uninitialized
1 = Jumper/ switch off, simulation not allowed
2 = Jumper/ switch on, simulation not allowed (need to cycle jumper/ switch)
64
Status of simulate jumper/switch.
51
The string will contain the following fields:
Major rev: 1-3 characters, decimal number 0-255
Minor rev: 1-3 characters, decimal number 0-255
Build rev: 1-5 characters, decimal number 0-255
Time of build: 8 characters, xx:xx:xx, military time
Day of week of build: 3 characters, Sun, Mon,...
Month of build: 3 characters, Jan, Feb...
Day of month of build: 1-2 characters, decimal number 1-31
Year of build: 4 characters, decimal
Builder: 7 characters, login name of builder
50
Build of software that the resource block was created with.
48
Major revision of software that the resource block was created with.
49
Minor revision of software that the resource block was created with.
63
0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications stack (no application data)
03
The strategy field can be used to identify grouping of blocks.
01
The revision level of the static data associated with the function block.
56
An enumerated value of repair analysis.
02
The user description of the intended application of the block.
08
Read/write test parameter - used only for conformance testing.
35
This alert is generated by any change to the static data.
40
This alert is generated if the write lock parameter is cleared.
34
If set, no writes from anywhere are allowed, except to clear WRITE_LOCK. Block inputs
will continue to be updated.
39
Priority of the alarm generated by clearing the write lock.
Block Information
C-11

Advertisement

Table of Contents
loading

Table of Contents