Emerson Rosemount 3051 Manual page 116

Transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Rosemount Model 3051 Transmitter with F
Status of the ADB
Figure C-5. Process Screen Capture
C-22
TM
fieldbus Protocol
OUNDATION
To launch the status screens in DeltaV Explorer right click on the
TRANSDUCER800 and select Status. The window under the Alarms
tab is a generic Transducer Block status screen and will not be
discussed here.
Process
Take note of the ADB status on the Process tab window. The ADB
status will change when the PIL status changes, only if the Affect PV
Status is "True" (see configuration).
Impulse Line
The Impulse Line tab contains the following information:
Time Stamp
Shows the timestamp of the last update to the Plugged Impulse Line
Status. NOTE: The current version of the DeltaV does not display
this field.