WLV
Actual access stage i (word level):
The access stage i, determined by the entry at input PSW, is output as binary value. For access
stage n, bit n is set to 1 and all of the other 15 bits, are set to 0.
e.g. for access level = 7, WLVcorresponds to 2#0000000001000000.
(Default: 2#0000000000000000)
WST
Device status (word state):
The actual device status STE is output as a binary value. For the current device status ST=n, bit
n is set to 1 and all of the other 15 bits are set to 0.
e.g. for STE=7, WST corresponds to 2#000000001000000.
(Default: 2#0000000000000001)
YTS
Status display:
7C72: Function block is configured several times
7CA9: no @FMPAR function block configured
7CC3: one or several incorrect entries were made at input PWi
7CC4: illegal entry at input STE
(Default: 0)
For additional values, refer to: D7-SYS online help "Help on events". (press
key F1 in the CFC and call-up the topic "Help on events" under
"CFC for SIMADYN D".)
Configuringdata
Function Blocks - FM 458-1 DP
Edition 12.2004
Computation time [µs]
Can be inserted online
Can be configured in
Executed in
Special features
FM 458-1 DP
3,3
--
Alarm-Tasks
Cyclic tasks
Initialization mode
Normal mode
Function block may only be configured once
per FM module
Function block additionally required on the
FM modules:
@FMPAR and PLIM
Communication blocks
2-41