5

SIMOLINK drive coupling

5.1

@SL SIMOLINK central block

Symbol
Hardware address SLB ―GV
Operating mode ― I
Node address ― I
Filling-up the telegram gaps ― BO
Use PCI Copy ― BO
Max. blocksize ― I
Enable the drive interface ― BO
Brief description
Mode of operation
Function Blocks - FM 458-1 DP
Edition 12.2004
@SL
TAD
MOD
ASL
Send power ― I
POW
FIL
DM
NSL
EN
The @SL central block allows the initialization and monitoring of
communications with an SLB module.
An SLB module is a system hardware component, which can be an ITSL-
, an EXM 448-1 module or an optional SLB (SIMOLINK Board) of the
ITSL module.
The @SL central block may only be configured in a cyclic task and once
per SIMOLINK ring.
The following parameters must be set for an SLB module:
• Hardware address SLB (TAD)
• Operating mode (MOD)
• Node address (ASL), only relevant when operating mode 0 is selected
• Send power (POW) for the SLB module
1. The @SL central block executes the following steps while the system
is being initialized:
− Checks the validity of the value ranges at the input connections
− Checks whether additional @SL central blocks have been
configured at the same hardware address (input TAD)
− Initializes the SLB module corresponding to the data at the
initialization connections
YF
I ― Error status of the block
NCP
I ― No. of nodes
NCY
DI ― No. of cycles
NOR
DI ― No. of overruns
NTO
DI ― No. of timeouts
NCR
DI ― No. of CRC errors
NDM
DI ― No. of the defective module
CO1
DI ― No. of waiting cycles
CO2
DI ― No. of CO1 overruns
QF
BO ― Group error bit