Slsvav Simolink Send And Receive Block For One Slave - Siemens FM 458-1 DP Manual

Function blocks
Hide thumbs Also See for FM 458-1 DP:
Table of Contents

Advertisement

5.7

SLSVAV SIMOLINK send and receive block for one slave

Symbol
Hardware addresse SLB
addresse of the slave
Number of send channels
Number of receive channels
setpoint at channel 0
setpoint at channel 1
setpoint at channel 2
setpoint at channel 3
setpoint at channel 4
setpoint at channel 5
setpoint at channel 6
setpoint at channel 7
Brief description
Mode of operation
Function Blocks - FM 458-1 DP
Edition 12.2004
SLSVAV
GV
TAD
I
ASL
I
NSV
I
NAV
DI
XS0
DI
XS1
DI
XS2
DI
XS3
DI
XS4
DI
XS5
DI
XS6
DI
XS7
A maximum of
• 8 setpoints and
• 8 actual values
can be transfered to and from one slave. The number of addressed
channels for the setpoints and the actual values is configured at the
inputs.
1. The SLSVAV send and receive block executes the following steps
while the system is being initialized:
• Checks the task assignment
• Initializes the task-list of the SLB module corresponding to the
data configured at the inputs
2. In the normal system mode ("RUN" mode), the SLSVAV send and
receive block executes the following:
• Checks that the inputs are within the permissible value range
• Enters the setpoints to be sent into the write buffer of the SLB
module
• Reads-out the actual values to be received from the receive
buffer of the SLB module
SIMOLINK drive coupling
YA0
DI
Actual value from slave 0
YA1
DI
Actual value from slave 1
YA2
DI
Actual value from slave 2
YA3
DI
Actual value from slave 3
YA4
DI
Actual value from slave 4
YA5
DI
Actual value from slave 5
YA6
DI
Actual value from slave 6
YA7
DI
Actual value from slave 7
SEQ
I
Sequence number
YF
I
Block error status
QF
BO
Group error bit