Option Card Slots

Installing PowerXL Series option board

Remove Utility line and control power from the drive.
Install the option board in one of the slots available on
the control board. To insert and remove the board, hold
it in a horizontally straight position to avoid twisting the
connector pins.
CAUTION
To prevent board damage, option cards and fieldbus boards
must not be installed, removed or replaced while utility line
or control power is applied to the drive.
4
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Verify the board fits tightly in the metal clamp and plastic
groove. If the board seems to be difficult to install in the slot,
you should confirm that you are using one of the allowed
slots for the option board.
N
ote:
Check that the DIP switch settings on the board corre-
spond to your need.

Control wiring

Digital I/O and 24 Vdc can use Stranded Cu or Solid Cu wire
as specified below. Analog signal PT100 must use shielded
cables. Table 2 shows the wire sizes available. I/O terminals
allow for 5.00 mm connectors.

Table 2. Wire sizes

Wire type
Wire size
Solid Cu –90 °C
12–28 AWG (0.2~2.5 mm
Stranded Cu –90 °C
12–30 AWG (0.2~2.5 mm
Terminal torque
2
)
4.5 in-lb (0.5 Nm)
2
)
4.5 in-lb (0.5 Nm)