Binary Value Objects
Property
Object_Identifier
Object_Name
Object_Type
Present_Value
Status_Flags
Event_State
Out_Of_Service
Inactive_Text
Active_Text
R: Read Property, W: Write Property, COVU: Unsolicited Change of Value Notification
Instance
Object_Name
1
"StartPCM"
2
"Fire"
3
"Window"
4
"ExtraTime"
5
"ActExtraTime"
6
"ActWindow"
7
"FAlarm"
8
"Alarm1"
9
"Alarm2"
10
"Release"
11
"Status_PowerSupply"
12
"Status_EMFSLIO"
13
"Status_Fan"
14
"Status_Sensor"
15
"Status_Filter"
16
"Status_FlowControl"
17
"Status_Damper"
18
"ActFire"
19
"FanForce"
20
"ActFanForce"
PICS_X-AIRCONTROL_v1.0.doc
Configuring interfaces to the central BMS
Remark / Value
binary-value, instance 1 ... 20
BINARY_VALUE (5)
INACTIVE (0, Initial) / ACTIVE (1)
IN_ALARM:
FAULT:
OVERRIDDEN:
OUT_OF_SERVICE:
NORMAL (0)
FALSE (0)
Inactive_Text
"Off"
"Normal"
"Close"
"Inactive"
"Inactive"
"Close"
"Normal"
"Normal"
"Normal"
"Off"
"Normal"
"Normal"
"Normal"
"Normal"
"Normal"
"Normal"
"Normal"
"Normal"
"Inactive"
"Inactive"
- 5 -
Single room control system FSL‑CONTROL II
0
0
0
0
Active_Text
"On"
"Fire"
"Open"
"Active"
"Active"
"Open"
"Frostalarm"
"Alarm1"
"Alarm2"
"On"
"LowPower"
"ComFail"
"FanBlocked"
"SensorFail"
"FilterAlarm"
"FlowAlarm"
"CalibrationFail"
"Fire"
"Active"
"Active"
BACnet MS/TP interface
RW
R
R
R
R
R
R
R
R
Present_Value
RW
RW
RW
RW
R
R
R
COVU
R
COVU
R
COVU
R
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
COVU
R
RW
R