nvoFanSpeed / ActFanSpeed
SNVT_switch
Function: Feedback of the fan stage (fan speed) to the central BMS
LON
state
value
1
1
1
1
1
1
0
0
0
0
0
0
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
Single room control system FSL‑CONTROL II
Configuring interfaces to the central BMS
BACnet
0
1
20
2
40
3
60
4
80
5
100
6
0
7
20
8
40
9
60
10
80
11
100
12
He, 21 March 2017
Modbus
Description
(Register 21)
1
Fan stage OFF,
manually
10241
Fan stage 1,
manually
20481
Fan stage 2,
manually
30721
Fan stage 3,
manually
40961
Fan stage 4,
manually
51201
Fan stage 5,
manually
0
Fan OFF,
automatic
operation
10240
Fan stage 1,
automatic
operation
20480
Fan stage 2,
automatic
operation
30720
Fan stage 3,
automatic
operation
40960
Fan stage 4,
automatic
operation
51200
Fan stage 5,
automatic
operation
List of data points