nvoSetPtOffset
SNVT_temp_p
Function: Feedback of a temperature offset to the central BMS
LON value
Enter as follows 3K 3
Invalid: 327,67
nvoRoomTemp / ActRoomTemp
SNVT_temp_p
Function: Feedback of the room air actual temperature to the central BMS
LON value
Enter with 2 decimal
places, e.g. 23 °C
23.00
Invalid: 327,67
nvoRelHumid / ActRelHumid
SNVT_lev_percent
Function: Feedback of the actual relative humidity in the room to the central BMS
(additional hardware required, or default setting by the central BMS)
LON value
-163.840....+163.830
Invalid: +163,830
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
Single room control system FSL‑CONTROL II
Configuring interfaces to the central BMS
BACnet value
Enter as follows 3K 3
Invalid: 327,67
BACnet value
Enter with 2 decimal
places, e.g. 23 °C
23.00
Invalid: 327,67
BACnet value
0....100%
Invalid: 65535
List of data points
He, 21 March 2017
Modbus value
(Register 24)
Enter without decimal
places, multiply with 100,
e.g. 3K  3
Invalid: 327,67
Modbus value
(Register 25)
Enter without decimal
places, multiply with 100,
e.g. 23.00 °C  2300
Invalid: 327,67
Modbus value
(Register 26)
0....100%
Invalid: 65535
13
53