Trox Technik FSL-CONTROL II Installation And Configuration Manual page 43

Single room control system
Table of Contents

Advertisement

nviOutsideTemp
SNVT_temp_p
Function: Default setting of outdoor air temperature by central BMS
LON value
Enter with 2 decimal
places, e.g. -12 °C -
12.00
Invalid: 327,67
nviTempOffset
SNVT_temp_p
Function: Default setting of room temperature setpoint (relative)
LON value
e.g. 3K 3
Invalid: 327,67
nviRoomTemp
SNVT_temp_p
Function: Default setting of room temperature
LON value
Enter with 2 decimal
places, e.g.
25 °C
25.00
Invalid: 327,67
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
Single room control system FSL‑CONTROL II
Configuring interfaces to the central BMS
BACnet value
Enter with 2 decimal
places, e.g. -12 °C -
12.00
Invalid: 327,67
BACnet value
e.g. 3K 3
Invalid: 327,67
BACnet value
Enter with 2 decimal
places, e.g.
25 °C
25.00
Invalid: 327,67
List of data points
He, 21 March 2017
Modbus value
(Register 3)
Enter without decimal
places, multiply with 100,
e.g. -12.00 °C  -1200
Invalid: 327,67
Modbus value
(Register 5)
Enter without decimal
places, multiply with 100,
e.g. 3K  300
Invalid: 327,67
Modbus value
(Register 6)
Enter without decimal
places, multiply with 100,
e.g. 25.00 °C  2500
Invalid: 327,67
3
43