Trox Technik FSL-CONTROL II Installation And Configuration Manual page 54

Single room control system
Table of Contents

Advertisement

Configuring interfaces to the central BMS
List of data points
nvoVOC_Room / ActVOC_Room
SNVT_ppm
Function: Feedback of the room VOC actual value to the central BMS (additional
hardware required, or default setting by the central BMS)
LON value
Invalid: 65535
nvoFrostAlarm
SNVT_switch
Function: Frost alarm
state
0
1
nvoAlarm1
SNVT_switch
Function: Consolidated alarm, category 1 (voltage monitoring and temperature
sensor failure)
state
0
1
54
0....65535
LON
value
XXX
XXX
LON
value
XXX
XXX
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
Single room control system FSL‑CONTROL II
BACnet value
0....65535
Invalid: 65535
BACnet
Modbus
(Register 28)
0
0
1
1
BACnet
Modbus
(Register 29)
0
0
1
1
He, 21 March 2017
Modbus value
(Register 27)
0....65535
Invalid: 65535
Description
Frost alarm
disabled
Frost alarm
enabled
Description
Alarm disabled
Alarm enabled