Configuring interfaces to the central BMS
List of data points
nvoEffectSetPt
SNVT_temp_p
Function: Feedback of the effective room temperature setpoint value to the central
BMS
Enter with 2 decimal
places, e.g. 26 °C
Invalid: 327,67
nvoWindow / ActWindow
SNVT_switch
Function: Feedback whether a window contact has been enabled
state
0
1
50
LON value
Enter with 2 decimal
places, e.g. 26 °C
26.00
LON
value
XXX
XXX
C:\Users\SCHMITHUESEN\Desktop\170321_Datenpunkte XAC_EN.docx
Single room control system FSL‑CONTROL II
BACnet value
places, multiply with 100,
26.00
Invalid: 327,67
BACnet
Modbus
(Register 20)
0
0
1
1
He, 21 March 2017
Modbus value
(Register 19)
Enter without decimal
e.g. 26.00 °C 2600
Invalid: 327,67
Description
Window
contact
disabled
Window
contact
enabled
10