3 SPECIFICATIONS AND FUNCTIONS
3.3.2 Details of input signal (QD70
Device
Signal name
No.
X0
Module READY
X1
Axis error
occurrence
X2
Axis warning
occurrence
X8
Axis 1
BUSY
X9
Axis 2
XA
Axis 3
XB
Axis 4
XC
Axis 5
XD
Axis 6
XE
Axis 7
XF
Axis 8
X10
Axis 1
Start
complete
X11
Axis 2
X12
Axis 3
X13
Axis 4
X14
Axis 5
X15
Axis 6
X16
Axis 7
X17
Axis 8
X18
Axis 1
Positioning
complete
X19
Axis 2
X1A
Axis 3
X1B
Axis 4
X1C
Axis 5
X1D
Axis 6
X1E
Axis 7
X1F
Axis 8
Important
: "Position control complete" of the QD70 refers to the point when the pulse output from
QD70 is completed.
Thus, even if the QD70's positioning complete signal turns ON, the system may continue
operation.
3 - 5

PLC CPU)

The ON/OFF timing and conditions of the input signals are shown below.
• When the PLC READY signal [Y0] turns from OFF to ON, the parameter and the
ON: Prepared
OFF: Not
OPR data setting range is checked. If no error is found, this signal turns ON. (When
prepared
the axis error occurrence signal [X1] is ON, this signal does not turn ON if the PLC
watch dog
READY signal [Y0] is turned from OFF to ON.)
• When the PLC READY signal [Y0] turns OFF, this signal turns OFF.
timer error
• When a watch dog timer (WDT) error occurs, this signal turns OFF.
• This signal is used for interlock in a sequence program, etc.
Module READY signal [X0]
• This signal turns ON if an error occurs in any of axes 1 to 8, and turns OFF when
OFF: No error
ON: Error
" Cd. 1 Axis error reset" is set for all axes.
occurrence
(Use " Md. 10 Error status" to confirm the error status of the corresponding axis.)
• This signal turns ON if a warning occurs in any of axes 1 to 8, and turns OFF when
OFF: No warning
ON: Warning
" Cd. 1 Axis error reset" is set for all axes.
occurrence
(Use " Md. 11 Warning status" to confirm the warning status of the corresponding
axis.)
• This signal turns ON at the start of positioning control, OPR control or JOG operation.
OFF: Not BUSY
ON: BUSY
It turns OFF when the " Da. 7 Dwell time" has passed after positioning control stops.
(This signal remains ON during positioning control.)
• This signal turns OFF at error or stop.
• This signal turns ON when the positioning start signal turns ON and the QD70 starts
OFF: Start
incomplete
the positioning control process.
ON: Start
(The start complete signal also turns ON during OPR control.)
complete
Positioning start signal [Y8]
Start complete signal [X10]
• This signal turns ON for the time set in " Pr. 7 Positioning complete signal output
OFF: Positioning
incomplete
time" from completion of position control of the corresponding axis.
ON: Positioning
(It does not turn ON if 0 is set in " Pr. 7 Positioning complete signal output time".)
complete
• While ON, this signal turns OFF if a positioning control start (including OPR control)
or JOG operation start is made.
• This signal does not turn ON at the termination of JOG operation.
(Refer to
• This signal does not turn ON if position control is stopped midway.
"Important")
PLC READY signal [Y0]
OFF
OFF
OFF
OFF
Description
ON
ON
ON
ON
MELSEC-Q
3 - 5