Summary of Contents for Mitsubishi QJ71AS92

  • Page 1 AS-i Master Module User’s Manual (Hardware) QJ71AS92 Thank you for purchasing the Mitsubishi programmable controller MELSEC-Q series. Prior to use, please read this and relevant manuals thoroughly to fully understand the product. MODEL QJ71AS92-U-H MODEL 13JT88 CODE IB(NA)-0800225-D(0807)MEE ©2002 MITSUBISHI ELECTRIC CORPORATION...
  • Page 2 SAFETY PRECAUTIONS (Always read these instructions before using this equipment.) Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product only. For the safety instructions of the programmable controller system, please read the user's manual for the CPU module to use.
  • Page 3 [Design Precautions] CAUTION Do not bunch AS-i cable with the main circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that would cause erroneous operation. [Installation Precautions] CAUTION Use the programmable controller in an environment that meets the general...
  • Page 4 [Wiring Precautions] DANGER Switch off all phases of the programmable controller power supply and AS-i power supply outside the programmable controller before starting installing or wiring work. There is a risk of electric shock or malfunction. CAUTION Always confirm the products terminal layout before wiring to the module. Incorrect wiring could lead to fires or faults.
  • Page 5 This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
  • Page 6: Table Of Contents

    CONTENTS 1. Overview ······································································································· 1 2. Performance Specifications ·········································································· 1 3. Loading and Installation ················································································ 2 3.1 Handling··································································································· 2 3.2 Installation Environment ··········································································· 3 4. Name and Setting of the Parts ······································································ 3 5. Wiring ··········································································································· 5 5.1 Precautions against wiring········································································ 5 5.2 Wiring·······································································································...
  • Page 7 (1) For programmable controller system To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller (EMC and Low Voltage Directives compliant) into other machinery or equipment, refer to Chapter 9 "EMC AND LOW VOLTAGE DIRECTIVES"...
  • Page 8: Overview

    1. Overview This manual explains how to handle the AS-i Master module, model number QJ71AS92 (hereinafter referred to as QJ71AS92). After unpacking the QJ71AS92, confirm that the following products are enclosed. Type Product Quantity QJ71AS92 type AS-i master module QJ71AS92 Connector 2.
  • Page 9: Loading And Installation

    *2: One slave uses four inputs and four outputs. One analog slave also uses four inputs and four outputs. For the general specifications of the QJ71AS92, refer to the user's manual of the used CPU module. 3. Loading and Installation The following section explains the precautions when handling the QJ71AS92, from the time they are unpacked until they are installed.
  • Page 10: Installation Environment

    3.2 Installation Environment Refer to user's manual of the CPU module used. 4. Name and Setting of the Parts Following is an explanation of the QJ71AS92 part names and settings. QJ71AS92 U ASI PRG ENA. ERR. S ERR. CODE MODE...
  • Page 11 Name Details Shows the error code or slave address of the QJ71AS92. Number Alphabet "CODE" LED Turned on/off to indicate the operating statuses of the QJ71AS92. LED name Color Details Lit when the module is normally operating. On = Normal operation...
  • Page 12: Wiring

    5.2 Wiring This clause explains wiring to the connector of QJ71AS92. Be sure connect the QJ71AS92 to the AS-i system with the AS-i cable. An example of wiring to the QJ71AS92 is shown below. (Confirm each module being used for the AS-i power supply and slave terminal layout.) Strip the AS-i cable about 7mm and plug it to the connector.
  • Page 13: External Dimensions Diagram

    6. External Dimensions Diagram QJ71AS92 U ASI PRG ENA. ERR. S ERR. CODE MODE ASI+ ASI- ASI+ ASI- (FG) QJ71AS92 27.4 (1.08) 90 (3.54) (0.47) Unit: mm (inch)
  • Page 14 Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi;...