CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

SAFETY INFORMATION

General Safety Information

When performing any work, all instructions given by the
manufacturer and in particular the safety instructions
provided in these Installation and Commissioning
Instructions are to be observed. Make sure that the local
standards and regulations are observed at all times.
The CIPer Model 50 System (including the CIPer Model
50 controller, Panel Bus I/O modules, manual
disconnect modules, and auxiliary terminal packages)
may be installed and mounted only by authorized and
trained personnel.
If the controller housing is damaged or missing,
immediately disconnect it from any power.
If the device is broken or defective, do not attempt to
repair it yourself; rather, return it to the manufacturer.
It is recommended that devices be kept at room tem-
perature for at least 24 hours before applying power.
This is to allow any condensation resulting from low
shipping / storage temperatures to evaporate.
The CIPer Model 50 System must be installed in such a
manner (e.g., in a lockable cabinet) as to ensure that
uncertified persons have no access to the terminals.
In the case of vertical mounting on DIN rails, the CIPer
Model 50 controller should be secured in place using a
commercially-available stopper.
If the CIPer Model 50 System is modified in any way,
except by the manufacturer, all warranties concerning
operation and safety are invalidated.
Rules regarding electrostatic discharge should be
followed.
Use only accessory equipment which comes from or has
been approved by Honeywell.

Information as per EN 60730

Purpose
The purpose of the device is: OPERATING CONTROL. The
CIPer Model 50 controller is a multifunctional non-safety
control device intended for HVAC in home (residential,
commercial, and light-industrial) environments.
Construction
The CIPer Model 50 controller is an independently
mounted electronic control unit with fixed wiring.
31-00233EFS-01
Mounting Method
The CIPer Model 50 controller is suitable for mounting as
follows:
in cabinets;
in fuse boxes conforming with standard DINX3880, and
having a slot height of max. 45 mm (1-64/83);
in cabinet front doors (using accessory MVC-80-AC2);
on walls (using accessory MVC-80-AC1).
Table 1. Information as per EN 60730
Shock protection
Pollution degree
Installation
Rated impulse voltage 330 V for SELV, 2500 V for relay
Automatic action
Software class
Ball-pressure test
temperature

WEEE Directive

WEEE: Waste Electrical and Electronic
Equipment Directive
At the end of the product life, dispose
of the packaging and product in an
appropriate recycling center.
Do not dispose of the device with the
usual domestic refuse.
Do not burn the device.

Standards, Approvals, etc.

Degree of Protection: IP20 (mounted on walls, with two
Device meets EN 60730-1, EN 60730-2-9, UL60730, and
UL916.
Refer to Code of Practice standards IEC 61000-5-1 and -
2 for guidance.
The device complies with Ethernet Protocol versions
IEEEC 802.3.
The device supports BACnet IP and BACnet MS/TP
communications as per ANSI / ASHRAE 135-2012.
2
Class II
2
Class 3
outputs
Type 1.C (micro-interruption for
the relay outputs)
Class A
housing parts >167 °F
terminals >257 °F
accessory MVC-80-AC1 covers)
IP30 (mounted in cabinet doors,
with accessory MVC-80-AC2)