Tuning Panel Bus Communication

The default polling interval for all Panel Bus points is set to "normal = 10s". Data from the field is thus updated every 10s.
Write commands are sent without time delay.
It is recommended that you update the polling interval of those points requiring more-frequent updating (see Fig. 40).
IMPORTANT
For CIPer Model 50, the fastest poll rate is 200 milliseconds.
Do NOT set a faster poll rate, as this may overload the CPU in larger systems.
Fig. 40. Editing the standard polling interval in "Poll Scheduler" of Property Sheet of PanelbusNetwork
CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
31