Wiring And Set-Up; General Safety Considerations; Lightning Protection; Wiring Terminals - Honeywell CIPer 50 Installation & Commissioning Instructions

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

WIRING AND SET-UP

General Safety Considerations

All wiring must comply with applicable electrical codes
and ordinances, including VDE, National Electric Code
(NEC) or equivalent, and any local regulations must be
observed. Refer to job or manufacturer's drawings for
details. Local wiring guidelines (e.g., IEC 364-6-61 or
VDE 0100) may take precedence over
recommendations provided here.
Electrical work should be carried out by a qualified
electrician.
Electrical connections must be made at terminal blocks.
For Europe, only: To comply with CE requirements,
devices with a voltage in the range of 50 ... 1000 VAC or
75 ... 1500 VDC which are not provided with a supply
cord and plug or with other means for disconnection
from the supply having a contact separation of at least
3 mm in all poles must have the means for
disconnection incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Observe precautions for handling electrostatic sensitive
devices.
Do not touch any live parts in the cabinet.
Do not open the controller housing.
Disconnect the power supply before making
connections to or removing connections from terminals
of the CIPer Model 50 controller and devices wired to it.
Do not use spare terminals as wiring support points.
To prevent risk of injury due to electrical shock and/or
damage to the device due to short-circuiting, low-
voltage and high-voltage lines must be kept separate
from one another.
All terminals are protected (up to 24 VAC) against short-
circuiting and incorrect wiring (unless the 3-position
slide switch is set to "END," in which case the terminals
of the RS485-1 bus [24, 25, and 26] have no such
protection). Higher voltages may damage the device.
Do not reconnect the power supply until you have
completed the installation.
Fusing Specifications
System Fusing
We recommend that the system be equipped with an
external fuse.
Fusing of Active Field Devices
F2 (depends upon given load).

Lightning Protection

Please contact your local Honeywell representative for
information on lightning protection.
31-00233EFS-01

Wiring Terminals

The CIPer Model 50 is equipped with push-in terminal
plugs.
Fig. 22. Inserting/removing wires from push-in terminals
NOTE: With solid conductors, ferrules are prohibited.
NOTE: Use only one conductor per push-in terminal.
NOTE: If, nevertheless, two stranded wires are to be
connected to a single push-in terminal, twin wire
end ferrules must be used.
Table 7. CIPer Model 50 push-in terminal wiring
plug gauge
solid conductor H05(07) V-K
stranded conductor H05(07) V-K
stranded conductor with wire end
ferrules (w/o plastic collar)
stripping length
16
specifications
0.2 ... 1.50 mm2
(0.0003... 0.002 inch2)
0.2 ... 1.50 mm2
(0.0003... 0.002 inch2)
0.2 ... 1.50 mm2
(0.0003... 0.002 inch2)
0.2 ... 1.50 mm2
(0.0003... 0.002 inch2)
10.0 +1.0 mm
(0.4" +0.04")

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents