SYSTEM OVERVIEW

Overview of Hardware

Feature
Description
NTC10kΩ / NTC20kΩ / 0...10V / slow BI, 0.4 Hz
UI
NTC10kΩ / NTC20kΩ / 0...10V fix pull-up / slow BI, 0.4 Hz
BI
open = 24 V / closed 2.0 mA / totalizer 15 Hz
AO
0..11 V (max. 1 mA)
Relay N.O. contact: 3 A, 250 VAC, 30 VDC
BO
Relay N.O. contact (high in-rush): 10 A, 250 VAC, 30 VDC
Relay N.O. contact with one common: 3 A, 250 VAC, 30 VDC
total I/Os
Bus
RS485-1, isolated, BACnet MS/TP, Panel Bus, or Modbus RTU
interfaces
Master or Slave communication
RS485-2, non-isolated, BACnet MS/TP, Panel Bus, or Modbus
RTU Master or Slave communication (NOTE: It is imperative
that the RS485-2 be powered by a power supply having the
proper polarity. Failure to do so will make data transmission
impossible.)
Ethernet Interfaces
BACnet IP communication, Niagara Network, Modbus TCP)
USB 2.0 Device Interface (as Network Interface)
USB 2.0 Host Interface (max. 200 mA)
RS232 M-Bus communication via 45-feet-long PW3 / PW20 /
PW60 converters
power LED (green)
status LED (red; indicates an active alarm; is controlled by
Niagara Alarm System; is configurable)
LED L1 (yellow; lit = Daemon starting; flashing = station
LEDs
starting; if L2 is also flashing, then the station has started)
LED L2 (yellow; lit = platform has started / is reachable; flashing
= station has started / is reachable)
bus status LEDs (for isolated RS485-1 interface)
Depending upon bit rate. However, in the case of configuration of RS485-2 for Panel Bus, the communication rate is set to
1)
115.2 kbps, and the max. cable length is hence 2400ft.
31-00233EFS-01
Table 3. Overview of models (hardware)
(
e-mail communication, browser access,
Max. cable
length
WEB-EAGLENx26ND
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
1200 ft
--
1)
3600 ft
1)
3600 ft
300 ft
9 ft
9 ft
1)
3000 ft
--
--
--
--
--
4
Order no.
without HMI
with HMI
WEB-EAGLENx26D
8
2
4
4
4
1
3
26
1
1
2
1
1
1
1
1
1
1
2
8
2
4
4
4
1
3
26
1
1
2
1
1
1
1
1
1
1
2